Server management 103

For multiple enclosures, FC bay groups will support FlexFabric modules similar to existing VC-FC modules.

FlexFabric module bay groups cannot contain any other type of VC-FC module, and any other VC-FC bay
group cannot contain a FlexFabric module. These module types are incompatible in the same bay group.
When an available port is used for Ethernet, it is no longer available for FC configuration, and vice-versa.

Likewise, a port that is removed from a network or fabric becomes available for configuration of another

network or fabric.
The FlexFabric VC module requirements also imply some additional constraints with current VC FC

requirements for bay groups. When a network is configured on a FlexFabric module using FC-capable ports,

those ports across the bay group are configured as Ethernet ports, becoming unavailable for FC. The similar

case applies when selecting the port type as FC.
There is a limitation on the NC551i LOM and the NC551m mezzanine card. FCoE and iSCSI connections

are not supported on the same adapter at the same time. By default, if a FlexFabric module is found in the

enclosure, FCoE connections are created for each server profile. If you do not wish to configure FCoE

connections, delete the default connections to allow the ports to be used for other connections, such as iSCSI.
To delete the connections, right-click the connection, and then select Delete Connection.
There are additional limitations with the supported LOMs and mezzanine cards that support FlexFabric

configurations. Both FCoE boot and PXE can be configured on the same port with the NC551i LOM and the

NC551m mezzanine card on different physical functions. Alternatively, iSCSI and PXE can be configured on

the same port. Only one PF can be configured for FCoE on a port.
When configuring FCoE connections, the port speed can be set to 1Gb, 2Gb, 4Gb, 8Gb, custom, or

disabled. The port speed is limited to a total of 10Gb, which must be shared between all defined connections

for that port. The custom speed allows you to better control the bandwidth between FC and Ethernet

connections. Valid custom speeds can be between 100Mb and 10Gb, in 100Mb increments. After all
connections are defined for a port, the actual allocated bandwidth will be calculated by VC Manager. For

bandwidth information see “Bandwidth Assignment (on page

107

)."

Upgrading or removing an HP Virtual Connect Flex-10 Module or
HP Virtual Connect FlexFabric Module

Upgrading an enclosure to Flex-10 or FlexFabric support or removing Flex-10 support requires several steps,
depending on the starting configuration.
Replacing a Virtual Connect Ethernet Module with an HP Virtual Connect Flex-10 Module or HP FlexFabric

Module in a horizontally adjacent bay pair hosting VC Manager (the horizontal bays housing primary

and/or standby modules)

CAUTION:

Replacing the primary/standby bay pair modules with modules of a different type

requires the creation of a new VC domain, creating the probability that VC managed identifiers

(MAC, WWN, and Serial Numbers) could be assigned to different server ports or slots from the
original VC domain.

1.

Upgrade the VC domain firmware to v3.15 or higher.

2.

Delete the domain.

3.

Remove all network uplinks from the modules to be removed.

4.

Remove the existing non-Flex-10 or non-FlexFabric modules from both horizontally adjacent bays.

5.

Install the HP Virtual Connect Flex-10 Modules or FlexFabric Modules.