3-4

IM 04L41B01-01E

• First-CH, Last-CH

Select the target channels.

• Range > Mode

Settings

Description

Skip

Not measured.

Volt, TC, RTD, DI, 1-5V

Input type. Represents DC voltage, thermocouple, RTD, ON/OFF

input, and 1-5V inputs, respectively.

Delta, Scale, Sqrt

Difference computation, linear scaling, and square root computation.

Set the items with check marks in the table below according to the mode value.

























































Volt

TC

RTD

DI

Delta Scale Sqrt 1-5V

Skip

Type

Range

Span Lower

Span Upper

Scale Lower

Scale Upper

Unit

Ref. CH

Low-cut

Low-cut value

Mode

Setup Item

• Range > Type

Input type when

Mode is Delta or Scale. See the description on Mode above.

• Range > Range

Input type details.

Standard

Standard

20mV

–20.000 mV to 20.000 mVDC

60mV

–60.00 mV to 60.00 mVDC

200mV

–200.00 mV to 200.00 mVDC

2V

–2.000 V to 2.000 VDC

6V

–6.000 V to 6.000 VDC

20V

–20.000 V to 20.000 VDC

20V

–50.00 V to 60.00 VDC

Pt

Pt100

JPt

JPt100

Level

ON/OFF(Voltage)

Contact ON/OFF(Contact)

1-5V

0.800V to 5.200V

R

Type R

S

Type S

B

Type B

K

Type K

E

Type E

J

Type J

T

Type T

N

Type N

W

Type W

L

Type L

U

Type U

WRe

type WRe

Setting

Input Type

Notes

Notes

Input Type

Setting

Cu10 (GE)

Cu10 (L&N)

Cu10 (WEED)

Cu10 (BAILEY)

Cu10: a = 0.00392 at 20

°

C

Cu10: a = 0.00393 at 20

°

C

Cu25: a = 0.00425 at 0

°

C

Cu1

Cu2

Cu3

Cu4

Cu5

Cu6

Cu25

Setting

Input Type

Notes

/N3

option

/N1

option

Kp

Kp vs Au7Fe

PLATI

PLATINEL

PR

PR40-20

NiMo

NiNiMo

W/WRe W/WRe26

N2

Type N (AWG14)

XK

XK GOST*

1

Pt50

Pt50

Ni1

Ni100 (SAMA)

Ni2

Ni100 (DIN)

Ni3

Ni120

J263

J263*B

Cu53

Cu53

Cu100

Cu100: a = 0.00425 at 0°C

Pt25

Pt25

Pt100G

Pt100 GOST*

1

Cu100G Cu100 GOST*

1

Cu50G

Cu50 GOST*

1

Cu10G

Cu10GOST*

1

Pt46G

Pt46 GOST*

1

Setting

Input Type

Notes

Pt200W

Pt200(WEED)

*2

*1 A function available on DXs with release number 3 or later.
*2 This function is available for release numbers 4 and later.

3.3 Setting the Input Range