7.3 Changing the Response to Remote Contact

Input Opening and Closing (/R1 and /PM1

options; release number 3 or later)

Set the remote contact input operation.

Setup Screen

Press

MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic

setting mode), and select the

Environment tab > Remote.

Setup Items

• Remote Input > 1 to 8

Specify an operation for each remote control terminal. Five remote control terminals

can be used for pulse input (/PM1 option).

Setting

Description

N.O

The remote signal rises when the contact input switches from open to

closed, and it falls when the contact input switches from closed to open.

N.C

The remote signal rises when the contact input switches from closed to

open, and it falls when the contact input switches from open to closed.

Type

Remote

contact

input

Operation

Control operation

N.C

N.O

Closed

Closed

Closed

OFF

ON

Open

Open

Open

Note

On models with the pulse input option (/PM1), the remote control input terminals can be
used for pulse input. When pulses are counted, the number of rising pulse edges is counted,
regardless of the Remote Input setting.