Data that can be used in equations, Processing order of computation, Handing of the unit in computations – Yokogawa Removable Chassis DX1000N User Manual

Page 57: Displaying the computed data, Alarm, Saving computed data

background image

1-46

IM 04L41B01-01E

• Data That Can Be Used in Equations

The data listed below can be used.

Data

Notation

Description

Measurement channel data 001, etc.

Specify the computed data using a channel number.

Computation Channel data

*1

101, etc.

Specify the computed data using a channel number.

Constant

K01 to K60

A value.

Communication input data

C01 to C24

Data set through communications.

Status of the remote control

input

*1

D01 to D08

*2

The value is 1 when the remote control input is ON

or 0 when it is OFF.

Pulse input

*1

P01 to P08

*2

Q01 to Q08

*2

Counts the number of pulses per scan interval.
Counts the number of pulses per second.

Internal switch status

S01 to S30

1 or 0.

Alarm output relay status

*1

I01 to I06

The value is 1 when activated or 0 when

deactivated.

Flag

*1

F01 to F08

1 or 0. Set the flag using the event action function

(see section 1.6).

Recording (memory

sampling) status

M01 to M06 The value is 1 when recording is taking place and

0 when recording is stopped. When the multi batch

function is not being used (release number 3 or

later; /BT2 option), M01 indicates the recording

(memory sampling) status. When the multi batch

function is being used, M01 to M06 indicate the

recording (memory sampling) statuses of each

batch. The recording status of an inactive batch

group is 0. This function is available for release

numbers 3 and later.

*

1 An option.

*2 Values such as 01 are terminal numbers.

Only the data that are checked in the table below can be used in TLOG, CLOG, and

PRE.

TLOG
CLOG
PRE
Other computations

Meas.

Channel

Data

Comp. Type

Comp.

Channel

Constant Comm.

Input

Remote

Pulse

Internal

Switch

Relay

Flag











Record

status

Example: TLOG.SUM(S01), CLOG.AVE(001.002.K01), and PRE(S01) are not allowed.

• Processing Order of Computation

Computation is processed in order from the smallest event action number for each

scan interval.

Example: If you specify 102 = 101 + 103, the value of the previous scan interval is

used for the 103 value.

• Handing of the Unit in Computations

In computations, measured values are handled as values without units. For example,

if the measured data from channel 001 is 20 mV and the measured data from channel
002 is 20 V, the computed result of 001 + 002 is 40.

• Displaying the Computed Data

The computed data is displayed by setting a measurement span for each computation

channel. Computation channels can be displayed on various operation screens in the

same fashion as the measurement channels.

For the setting procedure, see section 9.3.

• Alarm

Up to 4 alarms can be assigned to each computation channel. The alarm types are

high limit alarm (H), low limit alarm (L), delay high limit alarm (T), and delay low limit

alarm (t).

• Saving Computed Data

As with the measured data, the computed data can be saved to display data, event

data, manual sampled data, and report data.

1.8 Computation and Report Function (/M1 and /PM1 Options)