5-18

IM 04L41B01-01E

• Partial > Boundary

Set the value that is to be the boundary between the reduced section and the

expanded section in the range of “minimum span value + 1 digit to maximum span
value – 1 digit.” For channels that are set to scaling, the selectable range is “minimum
scale value + 1 digit to maximum scale value – 1 digit.”

Example: Input range: –6 V to 6V. Expand: 30. Boundary: 0

The –6 V to 0 V range is displayed in the 0% to 30% range, and the 0 V
to 6 V range is displayed in the 30% to 100% range.

5.9 Partially Expanding the Waveform