Measurement Channels and

Alarms

IM 04L41B01-01E

3-19

1

2

3

4

5

6

7

8

9

10

11

12

App

Index

0

0

1

1

1

2

2

P01

Number of pulses

per scan interval

102ch

Sum value

101ch

Reset count

Pulse input

Scan interval

Time

K01

reset value

(Resets the value below the reset value)

(Sum)

Channel 101: Reset Count

Calculates the number of times the pulse sum value is reset.
The expression “((102+P01).GE.K01)” is set to 1 when “the previous pulse sum value

(102) + the current pulse count (P01)” is greater than the reset value (K01). Otherwise,
the expression is set to 0. The value of channel 101 is incremented when the pulse
sum value exceeds the reset value.

Channel 102: Pulse Sum Value

Calculates the pulse sum value.
Under normal conditions, the pulse sum value TLOG.SUM (P01) is calculated. When

the pulse sum value is greater than or equal to the reset value (K01), the pulse sum
value is set to the amount exceeding K01.

Channel 103: Total Sum Value

Multiplies the reset value (K01) by the reset count (101) and adds the pulse sum value

(102) to derive the total sum value.

Note

• The computation is performed in order from the channel with the smallest channel number

in one scan interval. If the channel number in the expression is greater than or equal to the
channel number in which the expression is assigned, the previous computed result (previous
value) is used for the channel in the expression.

• If the pulse input value of the scan interval is greater than the reset value, correct

computation cannot be achieved.

3.10 Counting Pulses (/PM1 Option)