beautypg.com

Yokogawa Removable Chassis DX1000N User Manual

Page 175

background image

5-6

IM 04L41B01-01E

• Trend interval [/div] and Second interval [/div]

Select the time corresponding to 1 division of the time axis on the trend display from

below: You cannot specify a trend interval that is faster than the scan interval.

5s

*1

, 10s

*1

, 15s

*2

, 30s, 1min, 2min, 5min, 10min, 15min, 20min, 30min, 1h, 2h, 4h, and

10h

*1 Selectable on the DX1002, DX1004, DX1002N, and DX1004N (release number 3 or later).
*2 Selectable on the DX1006, DX1012, DX1006N, and DX1012N when the scan interval is set

to fast sampling mode (release number 3 or later).

Note

If the trend interval is set greater than or equal to 1h/div on a DX with release number 2 or later,
the month, day, and hour at the grid position are displayed on the screen. The display format
can be changed by setting the date format.

Month, day, and hour at the grid position.

Procedure

• Switching the Trend Interval

1.

In the operation mode, press

FUNC.

The FUNC key menu appears.

2.

Press the

Normal speed soft key or Second speed soft key.

The trend interval is switched. A message is written on the trend display (when the change
message is turned ON).
Display example: 10:53 1min/div

• Changing the Trend Display Time Axis While Recording (Memory

sampling) Is in Progress (Release number 3 or later)

On a DX whose release number is 3 or later, you can change the secondary trend

interval even while recording (memory sampling) is in progress. If you are using the
secondary trend interval to display waveforms and you change it, the time axis will
change immediately afterwards.

Note

Only the displayed time axis changes when you switch to the secondary trend interval. The
data sampling interval does not change.

5.3 Setting the Trend Interval and Switching to the Secondary Trend Interval

This manual is related to the following products: