beautypg.com

Setup items, Recording conditions of event data, Trend/save interval > second interval [/div – Yokogawa Removable Chassis DX1000N User Manual

Page 205

background image

6-2

IM 04L41B01-01E

• Recording Conditions of Event Data

Press

MENU (to switch to setting mode), and select the Menu tab > Data save >

Event data.

Setup Items

• Memory > Data kind

Settings

Description

Display

Records display data.

E+D

Records display data and event data. This setting cannot be selected when

the trend interval switching function is set to On. This setting cannot be

selected when the multi batch function (/BT2 option) is being used or on

DXs with the /AS1 advanced security option.

Event

Records event data.

• Memory sample > On/Off

Turn

On the target channels.

• Trend/Save interval > Trend interval [/div] (when recording display data)

See the table below. You can only set trend intervals that are longer than the scan

interval you set in Basic Setting Mode.

• Trend/Save interval > Save interval (when recording display data)

Select the size of a record data file. The recorded data is divided by the file size

specified here. The available settings vary depending on the number of memory
sampling channels and the

Trend interval setting.

Trend interval

*1

5 s

*2

10 s

*2

15 s

*3

30 s

1 min

Sample rate

125 ms

250 ms

500 ms

1 s

2 s

Selectable range

of auto save

interval

10 min to 12

hours

10 min to 1

day

10 min to 3

days

10 min to 7

days

10 min to 14

days

Trend interval

*1

2 min

5 min

10 min

15 min

20 min

Sample rate

4 s

10 s

20 s

30 s

40 s

Selectable range

of auto save

interval

10 min to 14

days

10 min to 31

days

10 min to 31

days

10 min to 31

days

1 hour to 31

days

Trend interval

*1

30 min

1 h

2 h

4 h

10 h

Sample rate

1 min

2 min

4 min

8 min

20 min

Selectable range

of auto save

interval

1 hour to 31

days

1 hour to 31

days

2 hours to 31

days

4 hours to 31

days

8 hours to 31

days

*1 You cannot set a trend interval that corresponds to a sampling interval that is faster than the

scan interval.

*2 Selectable on the DX1002, DX1002N, DX1004, and DX1004N (release number 3 or later).
*3 Selectable in fast sampling mode on the DX1006, DX1006N, DX1012, and DX1012N (release

number 3 or later).

• Trend/Save interval > Second interval [/div]

See section 5.3.

6.1 Setting the Recording Conditions of the Measured Data

This manual is related to the following products: