3.1 Setting the Scan Interval and the Integration
Time of the A/D Converter
Select the scan interval and the integration time of the A/D converter.
For a description of the scan interval and the integration time of the A/D converter, see
section 1.1.
Setup Screen
Press
MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic
setting mode), and select the
Menu tab > A/D, Memory.
Setup Items
• Scan interval > Scan mode
Normal: Measures at the normal mode scan interval.
* The scan mode is fixed at Normal when the multi batch function (/BT2 option; release
numbers 3 and later) is being used.
FAST: Measures at a scan interval of 25 ms (DX1002, DX1004, DX1002N, and
DX1004N) or 125 ms (DX1006, DX1012, DX1006N, and DX1012N).
• Scan interval > Scan interval
The selectable settings appear.
• Scan interval > A/D integrate
When the scan mode is set to
Normal, select the A/D integration time as necessary.
Only the selectable settings are displayed.
Settings Description
Auto
The DX automatically detects the power supply frequency and sets the integration
time to 16.7 ms and 20 ms for 60 Hz and 50 Hz, respectively. Fixed to 20 ms on
/P1 models that use the 24 VDC power supply.
50Hz
Sets the integration time to 20 ms.
60Hz
Sets the integration time to 16.7 ms.
100ms
Sets the integration time to 100 ms (when the scan interval is 2 s or 5 s).
600Hz
The A/D integration time for fast sampling mode. You cannot change this value.