Setup items, Logic box number, Event action > event – Yokogawa Removable Chassis DX1000N User Manual
Page 229
7-2
IM 04L41B01-01E
Setup Items
• Logic box number
You can set up to 40.
• Event action > Event
The condition to execute the action.
Settings
Description
None
Not use.
Remote
Select the remote control input terminal number.
Relay
Select the alarm output relay number.During Edge operation, a change from
deactivated to activated is an event.
Relay-Off
*2
Select the alarm output relay number. During Edge operation, a change
from activated to deactivated is an event. During Level operation, the action
states that correspond to “activated” and “deactivated” are the opposite of
when you select “Relay.”
Switch
Select the internal switch number.During Edge operation, a change from off
to on is an event.
Switch-Off
*2
Select the internal switch number. During Edge operation, a change from on
to off is an event. During Level operation, the action states that correspond
to “on” and “off” are the opposite of when you select “Switch.”
Timer
Select the timer number.
Matchtime
Select the match timer number.
Alarm
During Edge operation, a change from “no alarms are active” to “at least
one alarm is active” is an event
.Alarm-Off
*2
During Edge operation, a change from “at least one alarm is active” to “no
alarms are active” is an event. During Level operation, the action states that
correspond to “at least one alarm is active” and “no alarms are active” are
the opposite of when you select “Alarm.”
UserKey
-
Edge
*1
Select the event switch number (1 to 30). This function is available for
release numbers 3 and later
Level
*1
Select the event switch number (1 to 30). During Edge operation, a change
from off to on is an event.
LevelOff
*2
Select the event switch number (1 to 30). During Edge operation, a change
from on to off is an event. During Level operation, the action states that
correspond to “on” and “off” are the opposite of when you set the event to
“Level.”
*1 Available for release numbers 3 and later.
*2 Available for release numbers 4 and later.
7.1 Setting the Event Action Function (Including the remote control function of the /R1 and /PM1 options and