5

6

7

8

9

10

11

12

App

Index

Type

Example

Description of the Example

CLOG computation CLOG.SUM(001.002.003)

Determines the sum of [001], [002], and [003].

CLOG.MAX(001.002.003)

Determines the maximum value among [001], [002],

and [003].

CLOG.MIN(001.002.003)

Determines the minimum value among [001], [002], and

[003].

CLOG.AVE(001.002.003)

Determines the average value of [001], [002], and [003].

CLOG.P-P(001.002.003)

Determines the difference between the maximum value

and the minimum value among [001], [002], and [003].

Special computation PRE(001)

Determines the previous value of [001].

101=HOLD(001.GT.K01):TLOG.SUM(001)

Under normal conditions, TLOG.SUM(001) is carried

out to derive the computed value. When [001] exceeds

K01, the previous computed value is held.

K01

Description

HOLD(a):b

When a is zero, b is carried out to derive the computed

value. Otherwise, the previous computed value is held.

RESET(101.GT.K01):TLOG.SUM(001)

Under normal conditions, TLOG.SUM(001) is carried

out to derive the computed value. When [101] exceeds

K01, the previous computed value is reset, and

TLOG.SUM(001) is carried out.

K01

Reset

Description

RESET(a):b

When a is zero, b is carried out to derive the computed

value. Otherwise, the previous computed value is

reset, and b is carried out to derive the computed value.

CARRY(K01):TLOG.SUM(001)

Under normal conditions, TLOG.SUM(001) is carried

out to derive the computed value. When the computed

value is greater than or equal to K01, the computed

result is the excess (computed value – K01).

K01

Description

CARRY(a):b

Only TLOG.SUM can be specified for b. If the

computed value X of b is less than a, the computed

result is X. If X is greater than or equal to a, the

computed result is the excess (X – a).

Conditional equation [001.GT.K01?001:001+002]

When [001] is greater than K01, the computed value is

set to the value of [001]. Otherwise, the computed

value is set to the value of [001] + [002].

Description

[a?b:c]

If the computed result of a is nonzero, b is carried out.

Otherwise, c is carried out.