App index – Yokogawa Removable Chassis DX1000N User Manual
Page 230
7-3
IM 04L41B01-01E
Customizing
Actions Using the Event
Action and
Remote Control Functions (/R1 and /PM1 Options)
1
2
3
4
5
6
7
8
9
10
11
12
App
Index
• Event action > Action
The action to be executed when an event occurs.
Settings
Description
Memory
-
Start
-
Stop
-
Trigger*
Can be specified when the DX is configured to record event data.
AlarmACK Cannot be specified when the event is set to
Relay, Switch, or Alarm.
Math
Can be specified on /M1 and /PM1 options.
MathStrt
Start computation. Can be specified on /M1 and /PM1 options.
MathStop
Stop computation. Can be specified on /M1 and /PM1 options.
Math rst
Reset computation. Can be specified on /M1 and /PM1 options.
SaveDisp
Can be specified when the DX is configured to record display data.
SaveEvt
Can be specified when the DX is configured to record event data.
Message
Set the message number to write the message and the destination. Set the
message destination to all groups (All) or a group number.
Snap
Snapshot
Rate1/2
Can be specified when the function for switching between the trend interval and
the secondary trend interval is enabled.
M.sample
Manual sampling
TimerRst
Cannot be specified when the event is set to
Timer.
Group
Specify the number of the group to be displayed.
Flag
Can be specified on /M1 and /PM1 options.
Time adj
Can be specified only when the event is set to
Remote.
PnlLoad*
Can be specified only when the event is set to
Remote.
Comment
Specify the comment text block number to display. This function is available for
release numbers 3 and later.
Favorite
Choose which registered display to switch to. This function is available for release
numbers 3 and later.
Setting
Description
Key
Performs the same operation as
pressing the favorite key.
Select>Favorite Screen No Displays the specified favorite screen.
* If you configure the settings so that the Favorite action and the Group action
occur at the same time, only the action whose event action number is largest will
be executed.
AlarmRst
This action can only be specified when using the double lock-in sequence of the
alarm annunciator function (see section 3.12), and the event is Remote, UserKey,
or Edge. This function is available for release numbers 3 and later.
* This action is not available on DXs with the /AS1 advanced security option.
7.1 Setting the Event Action Function (Including the remote control function of the /R1 and /PM1 options and
the USER key)