beautypg.com

Yokogawa Removable Chassis DX1000N User Manual

Page 150

background image

Switching Operation Screens

4-23

IM 04L41B01-01E

1

2

3

4

5

6

7

8

9

10

11

12

App

Index

• Individual Alarm ACK Operation (Only on DXs with the /AS1 advanced

security option)

You can perform alarm ACK on individual alarms. This operation is referred to as

“individual alarm ACK.” Individual alarm ACK can be performed when the settings are
configured in the exact manner described below.
• Basic setting > Indicator is set to Hold.
For the setting procedure, see section 3.5.
• Relay > Relay Action on Ack is set to Reset.
For the setting procedure, see section 3.5 in the DX2000 User’s Manual.
• Annunciator Mode is set to Off.
For the setting procedure, see section 3.12 in the DX2000 User’s Manual.

1.

Use the

arrow keys to move the cursor to a channel with active alarms.

2.

Press

DISP/ENTER to show the display selection menu.

3.

Press the

right arrow key to display the submenu.

4.

Use the

arrow keys to select an alarm, and press DISP/ENTER.

The alarm output is released.

Select a channel with

active alarms.

Select the alarm that you

want to acknowledge.

4.4 Display the Statuses of All Channels on One Screen (Overview Display)