beautypg.com

App index – Yokogawa Removable Chassis DX1000N User Manual

Page 14

background image

1-3

IM 04L41B01-01E

Overview of Functions

1

2

3

4

5

6

7

8

9

10

11

12

App

Index

Difference computation

Low-cut

Square Root Computation

Calibration Correction (/CC1 Option)

Input

value

Measured

value

Measured

value

Input

value

Input

value

Input

value

Input

value

Measured

value

Measured

value

Measured value on the reference channel

The measured value of the channel is set to the

difference with respect to the measured value of the

reference channel.

Converts the unit to obtain the measured value.

Takes the square root of the input value and converts

the unit to obtain the measured value.

Corrects the input value with the characteristics

specified by segments to obtain the measured value.

Number of break

points: Up to 16

Pulse Input (/PM1 Option)

Linear Scaling

10 V

0 V

300 °c

–100 °c

a

b

x

a

b

B

B

X

A

A

X = (B – A)

+ A

x – a

b – a

The contact changes from open to close.

The signal level at the input terminal changes from high

to low.

5 ms or more

100 Hz or less

Pulse

Contact

or

Open

collector

Pulse that can be counted

Input to the DX

Count on the DX

Measured

value

Output

value

For square root computation, measured values below

the specified value are cut.

For 1-5 V input, values below 0 % are cut.

Result of square root

computation

Low-cut value

DX

For the setting procedure, see section 3.3.

For the setting procedure, see section 3.3.

For the setting procedure, see section 3.9.

For the setting procedure, see section 3.3.

For the setting procedure, see section 3.3.

For the setting procedure, see section 3.10.

( )

Note

Difference computation is executed even if the input type or range is not the same between
the difference computation channel and the reference channel. The difference is computed
discarding the decimal place and unit, and the decimal place and unit of the difference
computation channel are applied.

Example 1: If the input value of the difference computation channel is 10.00 and the measured

value of the reference channel is 100.0, the computed result is
10.00 – 100.0 = –90.00.

Example 2: If the input value of the difference computation channel is 10.00 V and the

measured value of the reference channel is 5.00 mV, the computed result is
10.00 V – 5.00 mV = 5.00 V.

Calibration Management (/CC1 option; release numbers 4 and later)

You can use this function to make sure that calibration is performed regularly.
When you enable calibration management, a screen (the calibration notification screen)
appears to notify you in advance that the calibration due date is approaching.
For the setting procedure, see section 3.13.

1.1 Input Section

This manual is related to the following products: