beautypg.com

Wiring ppc-2061 relay outputs, Wiring ppc-2062 relay outputs, Wiring ppc-2062 relay outputs 71 – Watlow PPC-2000 User Manual

Page 95: Figure 2.59—relay output connections on a ppc-2061, Outputs 1, 2, 9 and 10 shown 71

background image

PPC-2000 User’s Guide

Chapter 2: Hardware Installation

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

71

Wiring PPC-2061 Relay Outputs

The PPC-2061 has 16 normally open relay outputs. Outputs 1
to 8 share one common, and outputs 9-16 share the second
common. Either AC or DC may be switched. See Figure 2.59
for an example of how to connect to the relay outputs.

Table 2.23 on page 72 lists the connections to the PPC-2060 and
PPC-2061 modules.

Figure 2.59 Relay Output Connections on a PPC-

2061: Outputs 1, 2, 9 and 10 shown

WARNING!

Do not switch AC neutral (L2). Load switching must
occur on the hot (L1) side of the AC line. Failure to do
so could cause injury or death.

Wiring PPC-2062 Relay Outputs

The PPC-2062 has eight normally open, single-contact relay
outputs. The load may be connected to either contact. DC or AC
power may be switched. See Figure 2.60 on page 72 for an
example of how to connect to the relay outputs.

Relay 2

AC or DC
Source

Load

Relay 1

1

2

Load

C1

AC or DC
Source

Load

Relay 9

Relay 10

9

10

Load

C2

PPC-2061

L2 (AC)

L1 (AC)

L2 (AC)

L1 (AC)

Neutral or 120V

Neutral or 120V