Chapter 4: Troubleshooting

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

153

PPC-206x Digital Out

Refer to the following descriptions of LED indicators when
troubleshooting the digital output module.

Green Status LED remains off, on, or blinks
incorrectly:
When the module is correctly functioning the
green LED blinks. If the LED remains off, on, or blinks
incorrectly, the module may not be functioning correctly.

Corrective Actions:

Make sure the rotary switch is set to the proper module ad-
dress. Each module must have a unique address.

Cycle power to PPC-2000 system.

Check that the modules are connected properly; refer to
Module Assembly on page 24.

Perform a RAM clear; refer to Resetting Closed-Loop
Control Parameters on page 156
.

Replace the module.

Green Status LED is blinking but outputs are not
functioning correctly:

Corrective Actions:

Check to make sure the I/O wiring is correct. See Con-
necting to the Relay Outputs on the PPC-206x on page 70.

Check to make sure the digital outputs are correctly con-
figured. See Digital Inputs and Outputs on page 154.

PPC-207x Digital In

Refer to the following descriptions of LED indicators when
troubleshooting the digital input module.

Green Status LED remains off, on, or blinks
incorrectly:
When the module is correctly functioning the
green LED blinks. If the LED remains off, on, or blinks
incorrectly, the module may not be functioning correctly.

Corrective Actions:

Make sure the rotary switch is set to the proper module ad-
dress. Each module must have a unique address.

Cycle power to PPC-2000 system.

Check that the modules are connected properly; refer to
Module Assembly on page 24.

Perform a RAM clear; refer to Resetting Closed-Loop
Control Parameters on page 156
.

Replace the module.

Green Status LED is blinking but inputs are not
working correctly
:

Corrective Actions:

Check to make sure the I/O wiring is correct. See Con-
necting Digital Inputs to the PPC-207x on page 74.