Operating with AnaWin3

This section describes how to use your PPC system with
AnaWin3, the Watlow Anafaze HMI software. For hardware
installation and configuration information, refer to Chapter 2,
Hardware Installation
. For AnaWin3 installation and user
information, refer to the AnaWin3 User’s Guide.

Type

Definitions

In the following sections, a special font or typeface is used to
indicate text seen on the AnaWin3 screens:

Figure 3.1

Sample Screen Text

The words LP Enable and

LP Limit are shown as they appear in

AnaWin3.

Closed-Loop

Control

The PPC-2000 closed-loop control program can control up to 48
channels. Closed-loop control refers to the control of an output
based on feedback from a sensor or other signal.

LP Enable

Set this field to enable or disable the low process alarm. When
it is Enabled, the low process alarm activates if the process

variable (PV) dips below the

LP Limit.

The PV must rise above

the

LP Limit

plus the alarm deadband to be reset (cleared).

When this parameter is set to Disabled, the low process alarm

¡