beautypg.com

Watlow PPC-2000 User Manual

Page 175

background image

PPC-2000 User’s Guide

Chapter 4: Troubleshooting

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

149

Green Status and Error 3 LEDs remains on: Indicates
two or more modules are set to the same address.

Corrective Actions:

Change the rotary switch settings so that each module has
a unique address. Refer to Module Addresses on page 17.

Green Status LED remains off, on, or blinks
incorrectly:
If analog input scanning is properly
functioning, the green LED blinks. If the LED remains off,
on, or blinks incorrectly, the module is not functioning.

Corrective Actions:

Make sure the rotary switch is set to the proper module ad-
dress. Each module must have a unique address.

Cycle power to PPC-2000 system.

Check that the modules are connected properly; refer to
Module Assembly on page 24.

Perform a RAM clear; refer to Resetting Closed-Loop
Control Parameters on page 156
.

Replace module.

LED indicators are OK but inputs are not seen: Some
or none of the wired input data is being transferred to the
system. This may be an indication of a software or
hardware problem.

Corrective Actions:

Check all interconnects (terminal blocks and SCSI con-
nector).

Check the input configuration in the AnaWin3 software.
Refer to Chapter 3, Software Setup for configuration infor-
mation. Incorrect sensor type or wrong channel setup
could be seen as incorrect data retention.