beautypg.com

Table 3.12—anawin3 control types 118 – Watlow PPC-2000 User Manual

Page 142

background image

Chapter 3: Operating with AnaWin 3

PPC-2000 User’s Guide

118

Watlow Anafaze

Doc.# 30002-00 Rev 2.3

Control Type

Select the function of the channel. Refer to Table 3.12. Refer to
Heat and Cool Outputs on page 90 for more on PID1 and PID2.

Table 3.12

AnaWin3 Control Types

Heat/Cool Prop Band

Set the proportional band. Larger numbers result in less
proportional action for a given error or deviation from set point.
This parameter is set in engineering units.

Range: depends on the input type. See Table 3.15 on page 130.

Heat/Cool Integral

Enter the integral term value which controls the amount of
influence the history of error has on the output. Increasing the
integral value decreases the integral contribution to the
output. Entering an integral value of 0, however, yields no
integral action. This value is in seconds per repeat.

Range: 0 to 6000 seconds/repeat

Heat/Cool Derivative

Enter the derivative term value which controls the amount of
influence the rate of change of the error has on the output. A
greater value yields a greater derivative action. The derivative
constant is in units of seconds.

Range: 0 to 255 seconds

Control Type

Description

PID1

Heat and Cool outputs used to control.
Only one output may be on at a time.

PID2

Heat and Cool outputs used to control.
Both outputs can be on at the same time.

Retransmit

Choose this type to use the channel to
retransmit one or two analog inputs.