Table 7.12 digital output specifications, Table 7.13 serial interface – Watlow PPC-2000 User Manual
Page 263
PPC-2000 User’s Guide
Chapter 7: Specifications
Doc.# 30002-00 Rev 2.3
Watlow Anafaze
235
Table 7.12
Digital Output Specifications
** The PPC-2010 has 48 built-in digital I/O points. 24 points
are outputs only. 22 of the outputs are user configurable for PID
control, alarms or logic outputs. The other 2 outputs are
dedicated to system status and global alarm. The remaining 24
I/O points are individual configurable as either inputs or
outputs.
Table 7.13
Serial Interface
Number
48**
Configuration
1 global alarm
1 system status (CPU watchdog timer)
22 control outputs
24 configurable as inputs or control outputs
Max. Voltage
24Vdc
Max. Current
100mA sink to power common continuous
Off State Leakage Cur-
rent, Outputs 1 to 24
100µA
Off State Leakage Cur-
rent, Outputs 25-48
5µA
On State Maximum
Voltage
≤
0.7Vdc (output to common)
Number of Ports
2
Type
RS-232 3-wire or RS-485 5-wire
Modular Jacks
RS-232: 4 position, 4 conductor (phone handset)
RS-485: RJ12 6 position, 6 conductor
Isolation
40Vdc working, ± 200Vdc peak
Baud Rate
19200 default, configurable 9600 or 19200
Error Check
CRC
# of Controllers
1 with RS-232; 32 with RS-485
Protocol
Modbus RTU