Table 5.20
Output Types
Value
AnaWin3
Name
Description
Destinations
0
Time Prop
Digital, time
proportioned
Digital output from a
PPC-2010, PPC-2040 or
PPC-206x, Soft Bool
internal database value.
1
DZC
Digital, distributed
zero crossing
Digital output from a
PPC-2010 or PPC-2040
2
On/Off
Digital, on/off
Digital output from a
PPC-2010, PPC-2040, or
PPC-206x, Soft Bool
internal database value.
3-14
Reserved
15
Internal Count
Internal analog
software (register)
Soft Int internal database
value.Stored in the data-
base in the PPC-2010.
No additional hardware
required. Cannot drive
field I/O device directly.
16
Analog 0-20mA
Analog output type,
0-20mA
Analog output using a
PPC-2030 or PPC-2050
Soft Int internal database
value.
17
Analog 4-20mA
Analog output type,
4-20mA
18
Analog 0-5Vdc
Analog output type,
0-5Vdc
19
Analog 1-5Vdc
Analog output type,
1-5Vdc
20
Analog 0-10Vdc
Analog output type,
0-10Vdc
21
SDAC 0-20mA
Serial digital-to-ana-
log converter, 0-
20mA
Analog output using a
digital output from the
PPC-2010 module
connected to a peripheral
SDAC module.
22
SDAC 4-20mA
Serial digital-to-ana-
log converter, 4-
20mA
23
SDAC 0-5Vdc
Serial digital-to-ana-
log converter, 0-
5Vdc
24
SDAC 1-5Vdc
Serial digital-to-ana-
log converter, 1-
5Vdc
25
SDAC 0-10Vdc
Serial digital-to-ana-
log converter, 0-
10Vdc