beautypg.com

Connecting counter or frequency inputs, Connecting digital outputs – Watlow PPC-2000 User Manual

Page 65

background image

PPC-2000 User’s Guide

Chapter 2: Hardware Installation

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

41

Figure 2.21 Wiring Digital Inputs

Connecting Counter or Frequency Inputs

PPC-2010 module accepts a single-phase pulse signal from
devices such as encoders. Counts and frequencies of the inputs
may be scaled with user selectable parameters. See Setting up
User Selectable Linear Inputs on page 98
for more information.

The PPC-2010 module can accommodate encoder signals up to
24Vdc. The following figures illustrate connecting encoders:

Figure 2.22 Encoder with 5Vdc TTL Signal

Connecting Digital Outputs

The digital outputs sink current from a load connected to the
controller’s power supply, or another power supply referenced
to the PPC-2000 power common. Do not exceed +24 volts on the
outputs.

If you must tie the external load to ground, or if you cannot
connect it as shown in Figure 2.23 through Figure 2.25, use a
solid state relay to drive your load.

The outputs conduct current when they are LOW or ON. The
maximum current sink capability is 100mA at 24Vdc. They
cannot ‘source’ current to a load.

Digital

Input

Device

TB50

Digital In

Com

Frequency/Counter Input

Com

Encoder

+5Vdc

10 kOhm

TB50
PPC-2010

{Add examples with transistor inputs on
digital and pulse inputs.}