Wiring recommendations, Noise suppression, Wiring recommendations 35 noise suppression 35 – Watlow PPC-2000 User Manual
Page 59: Table 2.9—cable recommendations 35
PPC-2000 User’s Guide
Chapter 2: Hardware Installation
Doc.# 30002-00 Rev 2.3
Watlow Anafaze
35
ç
CAUTION!
Power, input or output circuits with hazardous voltage
levels should not have any live accessible parts.
Wiring Recommendations
Keep the following guidelines in mind when selecting wires and
cables:
•
Use stranded wire. (Solid wire can be used for fixed
service; but it makes intermittent connections when you
move it for maintenance.)
•
Use #20 AWG TC extension wire. Larger or smaller sizes
may be difficult to install, may break easily, or may cause
intermittent connections.
•
Use shielded wire. (The electrical shield protects the
signals and the PPC-2000 from electrical noise.) Connect
only one end of the shield to earth ground.
•
Use copper wire for all connections other than
thermocouple sensor inputs.
See Table 2.9 for cable recommendations.
Table 2.9
Cable Recommendations
Noise Suppression
The PPC-2000’s outputs are designed to drive resistive loads.
Open collector outputs can drive solid state relays. These relays
may in turn operate more inductive types of loads such as
Function
Mfr. P/N
No. of
Wires
AWG
Gauge
Max.
Length
Analog Inputs
Belden #9154
Belden #8451
2
2
20
22
RTD Inputs
Belden #8772
Belden #9770
3
3
20
22
TC Inputs
TC Ext. Wire
2
20
Digital PID Outputs
and Digital I/O
Belden #9539
Belden #9542
9
20
24
24
Analog Outputs
Belden #9154
Belden #8451
2
2
20
22
Computer
Communication:
RS232, RS422,
RS485, or 20mA
Belden #9729
Belden #9730
Belden #9842
Belden #9843
Belden #9184
4
6
4
6
4
24
24
24
24
22
4000 ft.
4000 ft.
6000 ft.