background image

PPC-2000 User’s Guide

Chapter 2: Hardware Installation

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

35

ç

CAUTION!

Power, input or output circuits with hazardous voltage
levels should not have any live accessible parts.

Wiring Recommendations

Keep the following guidelines in mind when selecting wires and
cables:

Use stranded wire. (Solid wire can be used for fixed
service; but it makes intermittent connections when you
move it for maintenance.)

Use #20 AWG TC extension wire. Larger or smaller sizes
may be difficult to install, may break easily, or may cause
intermittent connections.

Use shielded wire. (The electrical shield protects the
signals and the PPC-2000 from electrical noise.) Connect
only one end of the shield to earth ground.

Use copper wire for all connections other than
thermocouple sensor inputs.

See Table 2.9 for cable recommendations.

Table 2.9

Cable Recommendations

Noise Suppression

The PPC-2000’s outputs are designed to drive resistive loads.
Open collector outputs can drive solid state relays. These relays
may in turn operate more inductive types of loads such as

Function

Mfr. P/N

No. of

Wires

AWG

Gauge

Max.

Length

Analog Inputs

Belden #9154
Belden #8451

2
2

20
22

RTD Inputs

Belden #8772
Belden #9770

3
3

20
22

TC Inputs

TC Ext. Wire

2

20

Digital PID Outputs
and Digital I/O

Belden #9539
Belden #9542

9

20

24
24

Analog Outputs

Belden #9154
Belden #8451

2
2

20
22

Computer
Communication:
RS232, RS422,
RS485, or 20mA

Belden #9729
Belden #9730
Belden #9842
Belden #9843
Belden #9184

4
6
4
6
4

24
24
24
24
22

4000 ft.

4000 ft.

6000 ft.