beautypg.com

Linear 0-10vdc input example, Linear 4-20ma input example, Linear 4-20ma input example 101 – Watlow PPC-2000 User Manual

Page 125

background image

PPC-2000 User’s Guide

Chapter 3: Operating with AnaWin 3

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

101

Linear 0-10Vdc Input Example

For a sensor that measures pressures from 0.0 to 15.0 psia and
outputs a 0-10Vdc signal, set the following parameters:

Table 3.5

Scaling Parameters for 0-10Vdc
Linear Input Example

Linear 4-20mA Input Example

For a sensor that measures relative humidity with a range of
0.00 to 100.00% and outputs a 4-20mA signal, set the
parameters according to Table 3.6.

Table 3.6

Scaling Parameters for 4-20mA Linear
Input Example

Parameter

Setting

Units

Input Type

Linear -1 to 10 (v)

Units

psia

Input Signal Lo

0.000

V

Input Signal Hi

10.000

V

PV Lo

0.0

psia

PV Hi

15.0

psia

Decimal Places

1

Parameter

Setting

Units

Input Type

Linear -2 to 20 (mA)

Units

%

Input Signal Lo

4.000

mA

Input Signal Hi

20.000

mA

PV Lo

0.00

%

PV Hi

100.00

%

Decimal Places

2