Chapter 2: Hardware Installation

PPC-2000 User’s Guide

50

Watlow Anafaze

Doc.# 30002-00 Rev 2.3

A T/C is connected to a single-ended input by wiring the
positive signal lead to the

A

or

B

terminal and the negative

signal lead to the analog

COM

terminal. See Figure 2.32 and

refer to Table 2.13 on page 48.

WARNING!

Thermocouples connected to single-ended inputs
(PPC-2022) must be isolated (ungrounded) and
should not be embedded within heater elements as
some cartridge heaters are constructed.

.

Figure 2.32 Thermocouples Connected to

Single-ended Inputs 1 and 2

Connecting RTDs

Two-wire RTDs are connected between the

A

and

B

terminals

of the selected input. They may only be used with a differential
analog input module. A jumper wire must be added on the
terminal board from the

B

terminal to the

COM

terminal. See

Figure 2.33 on page 51.

frame ground

1A (input 1+)

Analog COM

2A (input 2+)

shield

(if present)

shield

(if present)

AITB