Watlow PPC-2000 User Manual
Page 201
PPC-2000 User’s Guide
Chapter 5: LogicPro and Modbus Reference
Doc.# 30002-00 Rev 2.3
Watlow Anafaze
175
* 16-bit binary number
NOTE!
Refer to Setting up Control Channels on page 92 for
the basics of setting up closed-loop control channels.
Process Variable Source (PV Source)
This variable determines the input used as the process variable
for this channel. The process variable is a hardware input
converted to engineering units. A value of 0 indicates a channel
with no input. See Table 5.13 on page 176 through Table 5.17
on page 179 for a list and explanation of input numbering.
Cool Limit Time
49
0-32767
41401-41450
578-5A9
Sensor Fail Heat%
37
0-1000
41001-41050
3E8-419
Sensor Fail Cool%
52
0-1000
41551-41600
60E-63F
Heat Output Filter
31
0-100
40701-40750
2BC-2ED
Cool Output Filter
46
0-100
41251-41300
4E2-513
Heat Output%
36
0-1000
40951-41000
3B6-3E7
Cool Output%
51
0-1000
41501-41550
5DC-60D
Heat Output Destination
40
0-4102
41151-41200
47E-4AF
Cool Output Destination
55
0-4102
41701-41750
6A4-6D5
Alarm Parameters
Alarm Status Flags
82
*
45451-45500
154A-157B
Alarm Control Flags
85
*
45601-45650
15E0-1611
Alarm Acknowledge
Flags
88
*
45751-45800
1676-16A7
Alarm Enable Flags
91
*
45901-45950
170C-173D
High Process Limit
80
45351-45400
14E6-1517
See explanation on p. 193
Low Process Limit
83
45501-45550
157C-15AD
High Deviation Offset
86
45651-45700
1612-1643
Low Deviation Offset
89
45801-45850
16A8-16D9
Alarm Deadband
92
0-255
45951-46000
173E-176F
Alarm Delay
93
0-100
46001-46050
1770-17A1
High Process Output
Destination
81
0-336
3103-4102
45401-45450
1518-1549
Low Process Output
Destination
84
0-336
3103-4102
45551-45600
15AE-15DF
High Deviation Output
Destination
87
0-336
3103-4102
45701-45750
1644-1675
Low Deviation Output
Destination
90
0-336
3103-4102
45851-45900
16DA-170B
Parameter
#
Range
Modbus
Address
Hex
Address
Notes