beautypg.com

Table 5.18—control mode 180 – Watlow PPC-2000 User Manual

Page 206

background image

Chapter 5: LogicPro and Modbus Reference

PPC-2000 User’s Guide

180

Watlow Anafaze

Doc.# 30002-00 Rev 2.3

Setpoint

The setpoint is the desired value for the process variable. The
setpoint may be set to any value within the range of the type of
the input selected as the Process Variable Source for the channel.
If the setpoint set is out of the defined range, the controller
assigns the closest number within the range.

Control Mode

This parameter indicates the mode of control for the channel.
Table 5.13 lists and describes the values to which this
parameter can be set.

Table 5.18

Control Mode

Heat/Cool Feedback Value

The raw output value in parts per thousand (0.1%) calculated
by the PID algorithm. In a normal control loops this value is
filtered with the output filter before it becomes the Heat Output
or Cool Output.

Heat/Cool Proportional Band (Heat/Cool Prop Band)

The proportional band is used to calculate PID output. Larger
numbers result in less proportional action for a given error or
deviation from setpoint. This parameter is set in engineering
units to a positive value less than the sensor range.

Heat/Cool Integral

The integral term controls the amount of influence the history
of error has on the output. Increasing the integral value
decreases the integral contribution to the output. Zero is a
special case that disables integral action. This value is in
seconds per repeat.

Value

Mode

Description

0

Off

Control algorithm is inactive and no output
is set.

1

Manual

Output is set by the user or a logic program.
See

Heat Output

and

Cool Output

in this

section.

2

Auto

Output is determined by the PID or on/off
control algorithm.

3

Tune

The PPC determines and sets the propor-
tional band, derivative and integral parame-
ters for the channel by setting the output
and measuring the system’s response. See

Autotuning on page 93

.