beautypg.com

Connecting sensors with linear voltage signals, Connecting sensors with linear voltage signals 52 – Watlow PPC-2000 User Manual

Page 76

background image

Chapter 2: Hardware Installation

PPC-2000 User’s Guide

52

Watlow Anafaze

Doc.# 30002-00 Rev 2.3

ç

CAUTION!

Do not connect the COM terminals on the AITB to
earth ground. Connecting COM to earth ground limits
the input protection to ±10Vac and could result in
damage to the input circuit.

Connecting Sensors with Linear Voltage Signals

For sensors with single output connections, connect the
negative input (

B

terminal) to the sensor common terminal.

Differential voltage transducers or sensors, such as bridges,
should be connected with the positive signal lead on the

A

terminal and the negative signal lead to the

B

terminal for the

selected input. See Figure 2.35.

Check sensor power supply connections and ground
connections to avoid exceeding the common mode range of the
Analog Input module or creating ground loops.

Figure 2.35 Connecting Linear Voltage Signals to

Differential Inputs 1 and 2

Single-ended voltage sources should have the positive lead on
the positive terminal of the desired input. The negative lead
should be connected to the

COM

terminal. See Figure 2.36 on

page 53.

Transducer

1A (input 1+)

1B (input 1-)

+

+

-

with linear

voltage

output

Transducer

with linear

voltage

output

2A (input 2+)

2B (input 2-)

COM

COM

AITB