Chapter 5: LogicPro and Modbus Reference

PPC-2000 User’s Guide

168

Watlow Anafaze

Doc.# 30002-00 Rev 2.3

Analog and Encoder Input Parameters

Table 5.8 lists the parameter number (#), range, and first and
last Modbus addresses for each analog input parameter. These
values are used when accessing analog input parameters with
third-party software, operator interface terminals or LogicPro
programs.

The range of some of the parameters depends on which input
type is selected. See Table 5.10 on page 170 for a list of the
input types and their corresponding ranges. While all the input
parameter values are 16-bit integers, many, such as Input Type,
are numerical representations of settings that have special
meanings to the controller. See the tables under the
corresponding parameter descriptions for explanations of the
possible settings.

Note that while any analog input can be assigned to any control
channel, the channel number that an input is assigned to has
no effect on the input variable’s data table address.

Table 5.8

Input Parameters

Parameter

#

Range

Modbus

Address

Hex

Address

Notes

Sample Time

74

200-700 ms

typical

31801-32200

708-897

Input,
Raw Counts

72

0-65535

31201-31600

4B0-63F

Input Value

67

-32768 to
+32767

30801-31200

320-4AF

Input Status

75

0-16

32201-32600

898-A27

See

Table 5.9

Input Type

60

0-60

41751-42150

6D6-865

See

Table 5.9

Input Filter

61

0-255

42151-42550

866-9F5

Temperature
Scale

64

0-1

42951-43350

B86-D15

See

Table 5.11

Input Signal Low

71

-32768 to
+32767

44551-44950

11C6-1355

See

Table 5.11

Input Signal High

70

-32768 to
+32767

44151-44550

1036-11C5

See

Table 5.11

Process
Variable Low

69

-32768 to
+32767

43751-44150

EA6-1035

Process
Variable High

68

-32768 to
+32767

43351-43750

D16-EA5

PV Offset/
Counter Reset

78

-32768 to
+32767

44951-45350

1356-14E5