Analog and Encoder Input Parameters
Table 5.8 lists the parameter number (#), range, and first and
last Modbus addresses for each analog input parameter. These
values are used when accessing analog input parameters with
third-party software, operator interface terminals or LogicPro
programs.
The range of some of the parameters depends on which input
type is selected. See Table 5.10 on page 170 for a list of the
input types and their corresponding ranges. While all the input
parameter values are 16-bit integers, many, such as Input Type,
are numerical representations of settings that have special
meanings to the controller. See the tables under the
corresponding parameter descriptions for explanations of the
possible settings.
Note that while any analog input can be assigned to any control
channel, the channel number that an input is assigned to has
no effect on the input variable’s data table address.
Table 5.8
Input Parameters
Parameter
#
Range
Modbus
Address
Hex
Address
Notes
Sample Time
74
200-700 ms
typical
31801-32200
708-897
Input,
Raw Counts
72
0-65535
31201-31600
4B0-63F
Input Value
67
-32768 to
+32767
30801-31200
320-4AF
Input Status
75
0-16
32201-32600
898-A27
Input Type
60
0-60
41751-42150
6D6-865
See
Input Filter
61
0-255
42151-42550
866-9F5
Temperature
Scale
64
0-1
42951-43350
B86-D15
Input Signal Low
71
-32768 to
+32767
44551-44950
11C6-1355
Input Signal High
70
-32768 to
+32767
44151-44550
1036-11C5
Process
Variable Low
69
-32768 to
+32767
43751-44150
EA6-1035
Process
Variable High
68
-32768 to
+32767
43351-43750
D16-EA5
PV Offset/
Counter Reset
78
-32768 to
+32767
44951-45350
1356-14E5