Encoder connections without the eitb, Encoder connections without the eitb 59, Table 2.18—hd-15 encoder signal connections 59 – Watlow PPC-2000 User Manual
Page 83
PPC-2000 User’s Guide
Chapter 2: Hardware Installation
Doc.# 30002-00 Rev 2.3
Watlow Anafaze
59
Figure 2.44 EITB Differential Quadrature
Connections: Input 1 and 2 Shown
Encoder Connections without the EITB
Encoders may be connected directly to the PPC-2030 module.
Table 2.17 and Table 2.19 on page 60 indicate the functional
pinout for HD-15 connectors connected to the Encoder In
Analog Out module connectors J1 and J2.
Table 2.18
HD-15 Encoder Signal Connections
1
The AnaWin3 name is shown for the Encoder In Analog Out module with address
11 on the first PPC-2000 in the system. Refer to Inputs on page 127 for a full
explanation of analog input naming. Both count and frequency are measured for
each input.
Module
I/O
Number
Connector and Pin
Number
AnaWin3 Name
(Input Spreadsheet)
1
Phase 1
Phase 2
+
-
+
-
Count 1
Frequency 1
J3-1
J3-2
J3-3
J3-10
PPC1:EIAO 11.1.1 C
PPC1:EIAO 11.2.1 F
Count 2
Frequency 2
J3-6
J3-7
J3-8
J3-11
PPC1:EIAO 11.1.2 C
PPC1:EIAO 11.2.2 F
Count 3
Frequency 3
J4-1
J4-2
J4-3
J4-10
PPC1:EIAO 11.1.3 C
PPC1:EIAO 11.2.3 F
Count 4
Frequency 4
J4-6
J4-7
J4-8
J4-11
PPC1:EIAO 11.1.4 C
PPC1:EIAO 11.2.4 F
Q1
1+
1-
Q2
2-
2+
1+
1-
2-
2+
8 (input 2 phase 1+)
9 (input 2 phase 1-)
10 (input 2 phase 2+)
11 (input 2 phase 2-)
2 (input 1 phase 1+)
3 (input 1 phase 1-)
4 (input 1 phase 2+)
5 (input 1 phase 2-)
12 (COM)
12 (COM)
EITB