beautypg.com

Modbus ascii and rtu modes, Message framing, Message framing 271 – Watlow PPC-2000 User Manual

Page 299: Table a.1—example message frame 271

background image

PPC-2000 User’s Guide

Appendix A: Modbus Protocol

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

271

Modbus ASCII and RTU Modes

Modbus protocol specifies two distinct modes: ASCII and RTU.
While the PPC-2000 only supports RTU, it is important to
understand the differences. Typically, ASCII is used for simple
communication tasks or diagnostics while RTU is used where a
more robust and efficient protocol is required.

The mode determines how messages are framed and coded. In
ASCII, each character in a message string is composed of a
hexadecimal character which is correlated to an ASCII
character. So for example, an ASCII message string contains
the value of a process variable, 5500 (550.0 degrees). 5500 in an
ASCII string is composed of 4 bytes, 35 35 30 30. 35 and 30 in
hexadecimal equate to the characters “5” and “0” in the ASCII
table respectively.

In RTU mode, the actual value is embedded in a message
string. There is no translation to ASCII characters. This results
in more compact message strings and efficient serial
communications. The value 5500 in an RTU string is composed
of its hexadecimal equivalent which is only 2 bytes, 15 7C.

Many host devices can communicate in either ASCII or RTU
mode. However, it should be noted that some PLCs can only be
an ASCII host.

Message

Framing

Messages start with a silent interval of at least 3.5 character
times. This is most easily implemented as a multiple of
character times at the baud rate that is being used on the
network (shown as T1-T2-T3-T4 in the figure below). The first
field then transmitted is the device address.

Networked controllers monitor the network bus continuously,
including during the silent intervals. When the first field (the
address field) is received, each device decodes it to find out if it
is the addressed device.

Following the last transmitted character, a similar interval of
at least 3.5 character times marks the end of the message. A
new message can begin after this interval.

Similarly, if a new message begins earlier than 3.5 character
times following a previous message, the receiving device will
consider it a continuation of the previous message. This will set
an error, as the value in the final CRC field will not be valid for
the combined messages. An example message frame is shown
in Table A.1.

Table A.1

Example Message Frame

Start

Address

Function

Data

CRC

Check

End

T1-T2-T3-T4

8 Bits

8 Bits

n X 8 Bits

16 Bits

T1-T2-T3-T4