Chapter 2: Hardware Installation

PPC-2000 User’s Guide

16

Watlow Anafaze

Doc.# 30002-00 Rev 2.3

Figure 2.2

PPC-IPS-2 Panel Mounting
Dimensions

To DIN rail mount the PPC-IPS-2:

1.

Locate a space with sufficient room for the power supply
and connecting wires. Refer to Figure 2.1 on page 15.

2.

Install a section of DIN rail.

3.

Hook the top of the DIN rail latch over the DIN rail such
that the spring is under the lip of the rail.

4.

Push down on the power supply, compressing the spring
then rock the bottom of the latch onto the rail.

To panel mount the PPC-IPS-2:

1.

Locate a space with sufficient room for the power supply
and connecting wires. Refer to Figure 2.2.

2.

Mark the mounting holes. See Table 2.3 on page 16.

3.

Drill and tap the mounting holes.

4.

Place the power supply such that the holes are aligned,
insert the screws and tighten them

Table 2.3

Power Supply Screw Mounting

PPC-IPS-2

Number of Screws

3

Drill and tap size

#6

0.24 in.

1.97 in.

1.32 in.

7.5 in.

7.84 in.

0.10 in.

0 79 i

0.93 in.

All

Vented

115