Table 5.62 system error log – Watlow PPC-2000 User Manual
Page 245
PPC-2000 User’s Guide
Chapter 5: LogicPro and Modbus Reference
Doc.# 30002-00 Rev 2.3
Watlow Anafaze
217
Table 5.62
System Error Log
Data-
base
Offset
Modbus
Address
Name
Description
1
33201
Error Count
Total error count (255 maximum)
22
33222
Logic Checksum
Bad checksum in a logic program hex record
24
33224
Logic Load
Error verifying programming of a logic program hex
record
42
33242
Undefined Parm#
Parameter number outside the range of the database
43
33243
Bad Data Sent
Attempt to write data outside of a parameter’s range
44
33244
Bad Offset
Parameter offset beyond last element of the parameter
45
33245
Parm Size
Internal error in parameter size during read or write
47
33247
Database Reg
Internal error registering database entry
48
33248
Write to RO
Attempt was made to write to a read only variable
49
33249
Change Q Overflow
Overflow in database change queue
51
33251
Bad Flash Type
Flash type was not found in table
52
33252
Flash Overflow
Attempted write past end of flash
53
33253
Program Verify
Failed program verify test
61
33261
Bad Interrupt
Received bad interrupt
66
33266
Divide by Zero
Divide by zero exception
67
33267
Illegal OpCode
Illegal opcode exception
71
33271
AI Address
Multiple AI boards detected at one address
73
33273
AI Cal Data
AI board has invalid calibration data
74
33274
AI Timeout
System unable to process AI input on time
75
33275
CMO or Open T/C
CMO or OTC occurred on an AI channel
92
33292
Bad Baud Rate
Configured baud rate not supported
93
33293
UART Not Found
A UART not detected
94
33294
Wrong Port
Internal error: attempt to configure unsupported port
96
33296
Closed Port
Internal error: attempt to access port that isn’t open
97
33297
Bad Parity
Internal error: attempt to configure unsupported parity
101
33301
Bad CRC
Modbus message CRC did not match
102
33302
Bad Modbus Func
Modbus message attempted unsupported function
103
33303
Invalid Address
Invalid Modbus register address
104
33304
Pckt Ln or Func
Bad Modbus packet length or diagnostic subfunction
107
33307
Packet Length
Bad Modbus packet length
108
33308
Bad Address
Bad Modbus register address
111
33311
Missed I/O Update
Internal error: missed I/O update deadline
129
33329
Bad Error Msg
Internal error: attempted to post error of 128 or greater