Panel mounting, Mounting terminal boards, Mounting terminal boards 28 – Watlow PPC-2000 User Manual
Page 52
Chapter 2: Hardware Installation
PPC-2000 User’s Guide
28
Watlow Anafaze
Doc.# 30002-00 Rev 2.3
Panel Mounting
The PPC modules may be panel mounted using the mounting
holes located on the end plates. The width of a system varies
depending on the number of modules. Consult Figure 7.1 on
page 230 to determine installed clearances.
To panel mount the modules:
1.
Locate a space with sufficient room for the appropriate
number of modules and connecting wires. Refer to Figure
7.1 on page 230 for a system footprint and dimensions.
2.
The mounting holes are located on the end caps of the
module assembly. Mark each mounting hole.
3.
Drill and tap the four #10 mounting holes.
4.
Place the modules such that the holes are aligned, insert
the screws and tighten them.
Mounting Terminal Boards
Terminal boards support interfacing field I/O devices with the
PPC modules. All terminal boards may be DIN rail or panel
mounted. The following sections provide procedures for
mounting the terminal boards.
There are smaller holes on each terminal board that may be
used to secure wiring with tie wraps.
Refer to Figure 2.13 on page 29 for AITB dimensions.