Table 7.28

Output Specifications

Table 7.29

Safety and Agency Approvals

Analog Outputs

4

Isolation

120Vac to power common or ground

Resolution

12 bits

Range (Voltage Mode)

0 to +10V @ 10mA maximum

Accuracy (Voltage Mode)

0.3% of reading
± 0.5% of range at 25°C

Load (Voltage Mode)

1000 ohm

Range (Current Mode)

0 to 20mA with 8V minimum
compliance (400 Ohm load)

Accuracy (Current Mode)

1.5% of reading
± 0.2% of range at 25°C

Output Update Time

0.1 sec.

UL
C-UL

3121-1 Listed, Category II Installation, File # E212113