beautypg.com

Watlow PPC-2000 User Manual

Page 219

background image

PPC-2000 User’s Guide

Chapter 5: LogicPro and Modbus Reference

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

191

Table 5.29

Alarm Bit Definitions

ç

CAUTION!

Failed sensor alarms are only checked on inputs
associated with channels. Any input that is not
selected as the

PV Source

of a channel will not

generate failed sensor alarms.

Alarm Control Flags

Each Alarm Control register contains a 16-bit word. The bits
determine the behavior of the various alarms. Setting an Alarm
Control
bit to 1 makes the corresponding alarm behave as a
control. Setting a bit to 0 makes it behave as a standard alarm.
Table 5.30 on page 192 describes the difference between
standard alarms and controls. See Table 5.29 for alarm bit
definitions.

Bit

Alarm Name

1 (least significant)

Spare

2

Spare

3

Low deviation

4

High deviation

5

Low process

6

High process

7

Spare

8

Spare

9

T/C break (or open)

10

RTD open

11

RTD short

12

Spare

13

Spare

14

Ambient Temperature

15

Spare

16 (most significant)

Spare