beautypg.com

Connecting sensors with linear current signals, Connecting sensors with linear current signals 53, Input 1, 2, and 3 shown 53 – Watlow PPC-2000 User Manual

Page 77

background image

PPC-2000 User’s Guide

Chapter 2: Hardware Installation

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

53

Figure 2.36 Connecting Linear Voltage Signals to

Single-ended Inputs 1 and 2

Connecting Sensors with Linear Current Signals

Differential current transducers or sensors should be
connected with the positive signal lead on the

A

terminal and

the negative signal lead to the

B

terminal for the selected

input. See Figure 2.37.

Figure 2.37 Connecting Current Inputs to a

Differential Input Module:
Input 1, 2, and 3 Shown

Single-ended current sources should be have the positive lead
on the positive terminal of the desired input. The negative lead
should be connected to the

COM

terminal. See Figure 2.38 on

page 54.

1A (input 1+)

A COM

2A (input 2+)

+

-

+

-

Transducer

with linear

voltage

output

Transducer

with linear

voltage

output

AITB

Typical

2-wire

current

transmitter

Typical

3-wire

current

sinking

transmitter

10 V Max

+ power

3A(Input 3+)

2A(Input 2+)

2B(Input 2-)

I

I

I

1A(Input 1+)

1B(Input 1-)

– power

Analog Com (optional)

+ power

28V Max

+ power

28V Max

Power
Supply

+

Typical

3-wire

current

source

transmitter

out

3B(Input 3-)