Disabling control, Disabling control 157 – Watlow PPC-2000 User Manual
Page 183
PPC-2000 User’s Guide
Chapter 4: Troubleshooting
Doc.# 30002-00 Rev 2.3
Watlow Anafaze
157
ç
CAUTION!
Do not perform this procedure at a time during which
closed-loop control and logic program outputs
should not be turned off.
1.
Remove power from the PPC-2000 system.
2.
Note the setting of the rotary switch on the Processor
Module.
3.
Set the rotary switch to position
E
.
4.
Power up the PPC-2000 system.
5.
Wait five seconds.
6.
Remove power from the PPC-2000 system.
7.
Set the rotary switch back to the position noted in Step 2.
8.
Power up the PPC-2000 system.
Disabling Control
If the settings in a PPC are not known it may be desirable to
power up the system in a state that will not generate outputs.
The following procedure describes how to power up the PPC-
2000 such that the closed-loop control and logic program, if any,
do not automatically begin:
ç
CAUTION!
Do not perform this procedure at a time during which
closed-loop control and logic program outputs
should not be turned off.
1.
Remove power from the PPC-2000 system.
2.
Note the setting of the rotary switch on the Processor
Module.
3.
Set the rotary switch to position
H
.
4.
Power up the PPC-2000 system.
5.
Set channels to the desired control modes to begin closed-
loop control.
6.
Click the Start Logic button on the PPC Globals screen to
start the logic program, if desired.