Global parameters in the database, Accessing global parameters with modbus, Global parameters in the database 206 – Watlow PPC-2000 User Manual
Page 234: Accessing global parameters with modbus 206, Table 5.46—soft bool and soft int registers 206, Table 5.46
Chapter 5: LogicPro and Modbus Reference
PPC-2000 User’s Guide
206
Watlow Anafaze
Doc.# 30002-00 Rev 2.3
These registers may be chosen as output destinations for a
channel. See Table 5.27 on page 190 for a list of output
destinations values that includes these registers.
Table 5.46
Soft Bool and Soft Int Registers
1
Use this address with the Soft_Bool or Soft_Int
IO Driver when addressing the Soft Boolean
and Soft Integer Registers.
Global Parameters in the Database
These system parameters are global and not relative to
channels or I/O hardware addresses.
Accessing Global Parameters with Modbus
Some global parameters have only one Modbus address others
use a range of addresses. Table 5.48 on page 208 and Table 5.51
on page 209 list first and last Modbus address for the global
parameters. Use Modbus addresses when accessing global
parameters with third-party software or operator interface
terminals.
See the parameter descriptions for addressing details.
AnaWin3 Name
(Soft Bool and Soft
Int Spreadsheets)
LogicPro I/O Physical
Address
1
Modbus Addressing
Decimal
Hex
PPC1: Soft Bool 1
PPC1: Soft Bool 2
PPC1: Soft Bool 1000
1
2
1000
3001
3002
4000
BB8
BB9
F9F
PPC1: Soft Int 1
PPC1: Soft Int 2
PPC1: Soft Int 100
1
2
100
46301
46302
46400
189C
189D
18FF
PPC1: Soft Int 101
101
47001
1B58
PPC1: Soft Int 102
102
47002
1B59
PPC1: Soft Int 2100
2100
49000
2327
…
…
…
…
…
…
…
…
…
…
…
…