Digital i/o uses – Watlow PPC-2000 User Manual
Page 227
PPC-2000 User’s Guide
Chapter 5: LogicPro and Modbus Reference
Doc.# 30002-00 Rev 2.3
Watlow Anafaze
199
Table 5.36
Addresses for Digital Inputs on the
PPC-207x Digital In Modules
1
The AnaWin3 names are shown for the first PPC-2000 in the system. See
132 for a full explanation of digital I/O naming.
2
LogicPro Variable Type must be BOOL.
3
Use this address with the
Digital_In_207x IO Driver when addressing
State
.
4
Use this address with the
Database IO Driver when addressing digital I/O parameters other
than
State
. Replace the # with the parameter number (#) from
Table 5.38 on page 200 for the
parameter you want to address.
Digital I/O Uses
The Processor module and the Digital I/O modules have 48
I/O points each. These modules have configurable I/O. Some or
all of their points can be individually configured as either an
input or an output by setting a bit in the Direction register.
24 of the 48 I/O points on the Processor module are
configurable. 22 I/O points are fixed as outputs. The remaining
two I/O points are reserved for the global alarm and CPU fail/
system OK signals.
Some I/O points can be used for frequency or counter inputs or
serial digital-to-analog (SDAC) outputs.
Refer to Table 5.37 on page 200 for specific information.
AnaWin3 Name
1
(Dig I/O Spread-
sheet)
LogicPro I/O Physical Address
2
Modbus Addressing
Digital_In_207x
IO Driver
3
Database
IO Driver
4
Database
Offset
Sample
Address
PPC1:DI 51.1
PPC1:DI 51.2
PPC1:DI 51.16
51.1
51.2
51.16
#.337
#.338
#.352
337
338
352
00337
00338
00352
PPC1:DI 52.1
PPC1:DI 52.2
PPC1:DI 52.16
52.1
52.2
52.16
#.353
#.354
#.368
353
354
368
00353
00354
00368
PPC1:DI 53.1
PPC1:DI 53.2
PPC1:DI 53.16
53.1
53.2
53.16
#.369
#.370
#.384
369
370
384
00369
00370
00384
PPC1:DI 54.1
PPC1:DI 54.2
PPC1:DI 54.16
54.1
54.2
54.16
#.385
#.386
#.400
385
386
400
00385
00386
00400
…
…
…
…
…
…
…
…
…
…
…
…
…
…
…
…
…
…
…
…