General pid constants by application, Proportional band only (p), Proportional with integral (pi) – Watlow PPC-2000 User Manual
Page 256: Pi with derivative (pid), General pid constants by application 228, Table 6.4—general pid constants 228
Chapter 6: Tuning and Control
PPC-2000 User’s Guide
228
Watlow Anafaze
Doc.# 30002-00 Rev 2.3
General PID Constants by Application
This section gives PID values for many applications. They are
useful as control values or as starting points for PID tuning.
Proportional Band Only (P)
Set the Proportional Band to 7% of the Setpoint.
(Example: Setpoint = 450: Proportional Band = 31).
Proportional with Integral (PI)
Set the Proportional Band to 10% of Setpoint.
(Example: Setpoint = 450: Proportional Band = 45).
Set Integral to 60.
Set Derivative to Off.
Set the Output Filter to 2.
PI with Derivative (PID)
Set the Proportional Band to 10% of the Setpoint.
(Example: Setpoint = 450: Proportional Band = 45).
Set the Integral to 60.
Set the Derivative to 15% of the Integral.
(Example: Integral = 60: Derivative = 9).
Set the Output Filter to 2.
Table 6.4 shows general PID constants by application.
Table 6.4
General PID Constants
Application
Proportional
Band
Integral
Derivative
Filter
Output
Type
Cycle
Time
Electrical heat with SSR
50°F
60
15
4
DZC
-
Electrical heat with EM relays
50°F
60
15
6
TP
20
Cool w/ solenoid valve
70°F
500
90
4
TP
10
Cool w/ fans
10°F
off
10
4
TP
10
Electric heat with open heat coils
30°F
20
off
4
DZC
-
Gas heat w/ motorized valves
SP>1200
60°F
100°F
120
240
25
40
8
Analog
-