The MRR is a data register in the PLC that allows the PLC to request screens for display

on the OIT. The OIT writes a zero to the MRR on initialization and reads the MRR every

200 msec. For more information on the MRR, refer to the Message Request Register

section in CHAPTER 2: Operational Overview.
10. In the Message Request Register group box, in the scroll box, specify the PLC

address for the MRR.

The Screen Stack stores PLC screen requests in a stack. This allows the OIT operator to

view the screens using the Next Message and Last Message keys. When the Screen Stack

is used, no screens are displayed on the OIT until the Next Message or Last Message

keys are pressed. For more information on the Screen Stack, refer to the Screen Stack

section in CHAPTER 5: Displaying Stored Screens. For this sample project, we will

disable the Screen Stack.
11. To disable the Screen Stack, in the Message Request Register group box, if the

Enable Message Stack check box is checked, select the Message Stack check box to

remove the check.

The CMR is a data register in the PLC that allows the PLC to determine which screen the

OIT is displaying. The OIT writes the current screen number to the CMR whenever the

screen changes. For more information on the CMR, refer to the Current Message Register

section in CHAPTER 2: Operational Overview. For this sample project, we will enable

the CMR and specify a PLC address.

12. To enable the CMR, in the Current Message Register group box, select the Enable?

check box.

13. In the Current Message Register group box, in the scroll box, specify the PLC address

for the CMR.

The MRR and CMR can be configured to use decimal or BCD format.
14. Specify the data format for the MRR and CMR.

To use decimal format, in the MRR/CMR Data Format group box, select the Use Decimal For-

mat for Data option button.

To use BCD format, in the MRR/CMR Data Format group box, select the Use BCD Format

for Data option button.

15. Choose the Done button to return to the OIT - Controller Settings dialog box.
16. Choose the Done button to return to the OITware-200 main screen.

Getting Started

9

1010-0099, Rev. 07

OIT3100 and OIT4100 Series
These OIT models allow the MRR to be disabled. For this sample project, we will

enable the MRR.
1. To enable the MRR, in the Message Request Register group box, if the Enable

check box is not checked, select the Enable check box.

These OIT models allow you to configure up to 32 “bit position” or “value” MRRs.

“Bit position” MRRs allow the PLC to request a screen by setting a bit instead of

writing a number. For this sample project, we will use a single “value” MRR. For

more information on using multiple or “bit position” MRRs, refer to the PLC Screen

Request section in CHAPTER 5: Displaying Stored Screens.
2. To disable the Enhanced Features, in the Message Request Register group box, if

the Use Enhanced Features check box is checked, select the Use Enhanced

Features check box to remove the check.