Maple Systems OIT Family User Manual
Page 104

OIT3165, OIT3175, OIT3185, OIT4165, OIT4175, OIT4185
The OIT3165, OIT3175, OIT3185, OIT4165, OIT4175, and OIT4185 have a factory
default setup mode keypad that is automatically activated when you enter setup mode
during power up. The factory default setup mode keypad is also activated when you enter
setup during operation (unless you specify the user-defined keypad as the setup mode
keypad in OITware-200).
NOTE:Do not specify the user-defined keypad as the setup mode keypad unless the
user-defined keypad includes the ENTER and TOGGLE keys. If you are using a setup
password, the numeric keys must also be included.
OIT3165, OIT3185, OIT4165, and OIT4185 Factory Default Setup Mode Keypad
OIT3175 and OIT4175 Factory Default Setup Mode Keypad
To specify the user-defined keypad as the setup mode keypad:
1. From the Configuration menu, choose Keyboard Settings, then choose User-Defined
Key Editor. The User-Definable Key Assignment dialog box appears.
2. In the Setup Mode Keyboard group box, select the Use Above Layout option button.
3. Choose the Done button to return to the OITware-200 main screen.
To enter setup mode:
1a. If the OIT is already powered, press the SETUP key once (on the user-defined keypad)
or the ENTER key three times (on the user-defined keypad).
The “Setup Password:” message should appear. At this point the factory default
setup mode keypad is active.
NOTE:It is possible to disable the ability to enter Setup mode by pressing the ENTER key three
times. In OITware-200, click on the Keypad icon
to display the Keyboard Settings
dialog box. Then check the Disable Run-Time Setup Access box. You will still be
allowed to enter Setup Mode by holding down the CLEAR key during power-up.
1b. If the OIT is not powered, while applying power to the OIT, press and hold the
bottom key on the right side of the keypad while the “<<< Initializing >>>”
message appears.
Other OIT Operating Modes
104