When the PLC Requests the Same Screen Twice the Screen is

Not Displayed

Possible Cause:

If the MRR already contained the screen number that the PLC requested, the OIT would

not recognize the screen request.

Possible Solution:

Modify the PLC program so that when the MRR already contains the screen number that

the PLC is requesting, the PLC writes a zero to the MRR before writing the screen number.

If using an OIT3100 and OIT4100 Series, activate the Clear Register/Bit After Receiving

Screen Request feature. Refer to the Configuring the MRR with Enhanced Features

section in CHAPTER 5: Displaying Stored Screens.

OITware-200

PC Displays “Out of Memory” When Starting OITware-200

Possible Cause:

The computer does not have sufficient resources to run OITware-200.

Possible Solution:

Use a computer that has at least 4MB of RAM.

OITware-200 Displays “Timeout Detected. OIT did not respond.”

Possible Causes:

The OIT is not connected to the PC or is not in Download/Upload Mode.

OITware-200 is not using the correct COM port.

The configuration cable is not wired correctly.

The configuration cable is not connected to the correct port on the OIT or the PC.

If your OIT has two serial ports, something is connected to the RTS/CTS lines on port 1.

Possible Solutions:

Verify that the configuration cable is wired correctly and is in good condition.

Follow the steps in the Downloading an OITware-200 Project section in CHAPTER 1:

Getting Started.

Ifyour OIThas two serialports,verifynothingis connectedto the RTS/CTSlines onport1.

OIT to PLC Communication

OIT Displays “Cannot Connect To PLC During Startup.

*** Reconnect in progress ***” or

“Can’t connect to PLC. Retry in Progress!”

Possible Causes:

The PLC’s mode switch is not in the correct position.

The PLC password in the OIT does not match the PLC.

The communication settings (baud rate, parity, data bits, stop bits) for the OIT and PLC do

not match.

The communication cable is not wired correctly.

The communication cable is not connected to the correct port on the OIT or PLC.

The wrong PLC protocol was downloaded to the OIT

Troubleshooting

122