Possible Solutions:

Verify that your PLC’s mode switch (if applicable) is in the correct position. The switch may need

to be in a mode other than run mode; such as terminal mode or xxxxxx mode. Refer to your

controlleroperationsmanualortheapplicableControllerInformationSheetfromMapleSystems.

Verify that the PLC password in the OIT matches the password in your PLC. In

OITware-200 press F4 to open the OIT - Controller Settings dialog box. In the Password

group box, enter the correct PLC password.

Verify that the communication settings in the OIT and PLC match. In OITware-200 press

F4 to open the OIT - Controller Settings dialog box. In the OIT - Controller Serial

Communications Settings group box, select the correct communication settings.

Verify that the communication cable is wired correctly and in good condition.

Verify that the OIT and PLC are connected correctly. Refer to the Installation Manual that

came with the OIT.

Download the project with the correct PLC protocol from OITware-200. Follow the steps

in the Downloading an OITware-200 Project section in CHAPTER 1: Getting Started.

OIT Displays “Cannot write to Msg Request Register!” or “Er-

ror: Setting up Mailbox During Startup”

Possible Cause:

The PLC address for the Message Request Register (MRR) is outside the memory

supported by the PLC’s CPU.

Possible Solution:

Change the PLC address for the MRR. In OITware-200 press SHIFT+F6 to open the OIT

Message Control Settings dialog box. In the Message Request Register group box, select a

supported PLC address. If you are using the MRR enhanced features, to set the PLC

address(es) for the MRR(s), refer to the Configuring the MRR section in CHAPTER 5:

Displaying Stored Screens.

OIT Displays “Cannot write to the Status Coils!” or

“Error: Setting up StatusCoils On Startup” or

“Cannot set the Reset Status Coil!” or

“Error: Setting STAT_RESET during Startup” or

“Cannot set the Alarm Empty Status Coil!” or

“Error: Setting ALM_EMPTY During Startup”

Possible Cause:

The PLC address for the Status Coils is outside the memory supported by the PLC’s CPU.

Possible Solution:

Change the PLC address for the Status Coils. In OITware-200 press F4 to open the OIT -

Controller Settings dialog box. In the Status Coils group box, select a supported PLC

address.

OIT Displays “Cannot write to the Function Key Coils!” or

“Error: Setting up KeyCoils On Startup”

Possible Cause:

The PLC address for the Function Key Coils is outside the memory supported by the

PLC’s CPU.

Possible Solution:

Change the PLC address for the Function Key Coils. In OITware-200 press F5 to open the

Function Key Editor dialog box. In the Coil Address group box, select a supported PLC

address.