beautypg.com

Con trol keys 79, Arrow keys 79, Control keys – Maple Systems OIT Family User Manual

Page 79: Alarm acknowledge, Arrow, Delta+ & delta

background image

3. In the Action drop down list box, choose the action you want this screen dependent

function key to perform.

4. If you selected Push On/Off, Momentary, or Latched, in the Address group box,

select the PLC coil address to use for this screen dependent function key.

5. If you selected Screen, Dnload Recipe, or Upload Recipe in the Screen scroll box,

select the stored screen number to display when this screen dependent function key is

pressed.

6. If you selected Screen, Dnload Recipe, or Upload Recipe and want to use the

password feature, in the Password drop down list box, select the appropriate password

level. For more information on passwords, refer to the Passwords section in this

chapter.

7. Choose the Done button to return to the Screen-Dependent Function Key Editor dialog

box.

8. Choose the Done button to return to the OITware-200 main screen.

Control Keys

Following is a description of how each control key operates. If you are configuring an

OIT3100 or OIT4100 Series product, except OIT3160 or OIT4160, you should use the

requirements paragraphs when deciding which keys to place on your user-defined

keypad.

Alarm Acknowledge

The ALARM ACKNOWLEDGE key is used to acknowledge the alarm currently in

progress and remove it from the alarm stack.
Requirements: If using alarm screens, the ALARM ACKNOWLEDGE key is required

unless you use the PLC to clear the alarms. Using the PLC to clear alarms is not

recommended, since there will be no way to know if the OIT operator saw the alarm.

Arrow

The arrow keys are used to move the cursor from one read/write PLC register monitor to

another. Each time one of the arrow keys is pressed, the cursor moves to the next closest

read/write PLC register monitor in the direction of the pressed arrow key. When the

cursor is located at one of the edges of the display, additional keypresses in the direction

of the display edge cause the cursor to wrap around.
Requirements: If using read/write PLC register monitors, either the right arrow key or

left arrow key is required. Additional arrow keys can reduce the keypresses required to

access certain read/write PLC register monitors on the screen, but are not necessary.

Delta+ & Delta-

The DELTA+ and DELTA- keys are used in read/write PLC register monitors that have

been configured with a preset increment/decrement value. When the cursor is on a

read/write PLC register monitor with a preset increment/decrement value, the DELTA+

key increments the value in the PLC register monitor on the screen by the preset value

and the DELTA- key decrements the value. These changes are immediately written to the

PLC register. If pressing the DELTA+ or DELTA- key causes the value in the PLC

register monitor to bump against the preset low or high limit, the key is ignored.

Key Types

79