Module Sense of Action:
The module sense of action (controller sense of action) is reversible. The module sense of action is
normally not inverted.
The module sense of action can be changed via the configuration file or in the menu item
"Configuration" - see the following figure.
Figure 30: Sense of action of the
module (COMMON_PID).
Effective direction of the actuator
The control output calculated by the controller can be adapted with this function to the effective
direction of the actuator according to the following figure.
- Rise:
Direct effective direction
- Scenario:
Inverse effective direction
Control Output
Control Output
calculatd by
Controller
100%
0%
100%
0%
Fall
Rise
Figure 31: Effective direction of the
actuator (COMMON_PID).
If the connected actuator - when using a proportional controller with Start point (X0) 0% in the
compensated state
• shall be selected with 0%
Æ Select effective direction Rise
• shall be selected with 100%
Æ Select effective direction Fall
Control output limitation
The output control output is only restricted in the automatic mode through the control output limit.
Either characteristic curve 1 or 2 (charact 1 or 2) can be chosen for the limit.