Burkert Type 8620 User Manual
Page 147

mxCONTROL Type 8620
Page 147
Warning or
Error message
Displayed as
Displaying
interval
Cause
Remedy
XX = 01 … 08, 21, Y = 1:
The cause is often a power-
on-reset or software reset
while updating Eeprom
values.
Report this error to Bürkert
Sales Center.
All other errors:
Proceed as for XX = 00,
Y = 1. If this error occurred
more than once, then the
device has to be replaced.
Contact the Bürkert Sales
Center regarding replacing
the device.
Email failed
short message
Error while communicating
with SMTP server -
transmission of email failed.
Refer to error message
“SMTP Error X Y”, which
was displayed before.
Error ISR
Timing X
permanent
message
once
Internal Timing Error in
cyclical executed function.
Contact your local Bürkert
Sales Center and provide
the current configuration
and parameter files.
Factory Reset
short message
once
All configuration and
parameter data is reset to
default values and the
mxCONTROL can initially no
longer work as controller.
The continuation of the
operating as controller is
possible after the downloa-
ding of a new configuration
and parameterization.
False code
short message
once
Wrong code for current
required code level.
Access to target menu item(s)
is denied.
Input the right code for the
required code level.
Fault Ethernet
permanent
message
Once each
minute - as
long as fault
is not
remedied or
Ethernet
function is
disabled
Communication with internal
Ethernet module failed.
Contact the Bürkert Sales
Center if the error occurs
more often.
Fault RTC
short message
permanent
message
once
once
Communication with internal
RTC failed. Time is generated
internally.
Initialization of RTC failed or
RTC delivered inconsistent
time.
Contact the Bürkert Sales
Center if the error occurs
more often.
Set the clock. Then restart
the device. If the error
occurs again (more than 3
times), contact the Bürkert
Sales Center.
Input Fault
(Input state: FI)
Icon in menu
Processdata/
Inputs
Icon/flashing
message in full
screen view of
correspondent
Process Value
as long as
fault is not
remedied
Analog input:
4…20 mA: Current below
approx. 3.5 mA
Pt100:
Resistance < input range or
Pt100 not connected
Check the wiring from the
corresponding sensor to
mxCONTROL.