1 download – Burkert Type 8620 User Manual
Page 37
mxCONTROL Type 8620
Page 37
Most modules have a spezial ”Output Override“-Function (override the original output value) in
order to react to situations as:
- Input or Sensor Faults,
- Activation of the System or Flow Switch or
- special states or alarms of other activ modules.
Output Prozess:
• Converting and transferring of the virtual module outputs to the configured real outputs (that
means the real outputs are controlled to output the configured form of output signal)
11.2
Up- and Downloading of Configuration/Para-
meter Files
11.2.1 Download
For the Download process proceed as stated below
(see also the sample menu tree in the appendix 21.5.6):
→ Supply the „Type 8620 mxCONTROL“ with power
→ Insert
an
SD card (formatted with FAT16)
into the interface (SD card slot)
under the hinged lid
→ Scroll in the main menu to the menu item “Up-/Download” (via “arrow” keys),
press key “ENTER”.
→ Enter
the
correct password
(via keys „+“ and „<-“)
(
specialist password for configuration files,
operator or specialist password for parameter files).
→ Select
“Download”
, press key “ENTER”
→ Navigate via arrow keys to file folder containing the desired configuration or
parameter file.
Return to parent folder by scrolling to ".." or
open a folder by pressing the key "ENTER".
To furnish the „Type 8620 mxCONTROL“ with a new configuration, first
the configuration file
must be downloaded to the device, followed by the
corresponding parameter file.
Before the „Type 8620 mxCONTROL“ can act in an automation system, a configuration file
must be downloaded to the device (e.g. from the SD card).
(The last downloaded configuration and parameter file defines the function of the „Type 8620
mxCONTROL“!)
This is for the Specialist Level only!
Up-/Download processes on SD-Card are only possible if Data Logging is disabled.