Processdata and data logging, Parameter (codelevel: operator) – Burkert Type 8620 User Manual
Page 101

mxCONTROL Type 8620
Page 101
Processdata and Data Logging
Display-Presentation
Displayed data
Abbre-
viation
(menu)
Full
Screen
Trend
chart
Line
Data-
Log.
Notes
Process value
PV
x x x
x
Process value (in ppm)
PV
x x
x
Only if TDS-Display
is configured
Set point
SP
x x
x
Set point vs. Process value
SP/PV
x
Module output
CMD
x x
x
MOT Alarm
(Maximum Output Timer Alarm)
x
x
is displayed only if
MOT was enabled
and is expired;
Data log in controller
output
Parameter (CodeLevel: Operator)
Parameter
Abbrevia-
tion
(menu)
Value range
Default values
(after successful download of
Cfg-File)
Sample Time
Tsample
0.05/0.1 … 60.0 s
0.2 s
Set point
SP
Scal- …Scal+ of the
assigned input
Scal- + ((Scal+ - Scal-) /2)
Gain/amplification factor
Kp
0.001 … 9999.0
(in % / unit)
10.0
Reset time
Tn
0.1 ... 9999.0 s
9999.0 s
Lower output limit
Lim-
0.0 % ... Lim+
0.0 %
Upper output limit
Lim+
Lim- ... 100.00 %
100.00 %
3-point step output (*):
Period for opening the actuator from
position 0% to 100%
Tco op
1 ... 600 s
60 s
3-point step output (*):
Period for closing the actuator from
position 100% to 0%
Tco cl
1 ... 600 s
60 s
3-point step output (*):
Process switching difference
Psd
0.01 ... 20.00 %
2.0 %
Safety output value
CMDsafe
0.0 ... 100.00 %
0.0 %
Maximum output timer (MOT)
Maximum output time (**)
+Tm
1 ... 10800 s
10800 s
For TDS-Calibration:
Conductivity value (***)
PV cal
1 ... 99999 (in units of
the assigned process
value input)
1000
TDS value (***)
TDS cal
1 ... 99999 ppm
800 ppm
(*) will be only displayed if the parameter “3PS” is configured as “Yes” in the menu „Configuration“
(**) will be only displayed if the parameter “MOT” is configured as “Yes” in the menu „Configuration“
(***) will be only displayed if the parameter “TDS Disp” is configured as “Yes” in the menu „Configuration“